Check and make sure there isn’t open phase condition for the AC input voltage, the module isn’t working in high temperature environment, and the module address isn’t repeated. After that, the module can be back to normal.
Disconnect the module from AC power for 1 minute, and reboot the module after making sure there is no power in it; replace EEPROM in the DC controller if the problem still exists.
Make sure the wires and grids are working normally and the module input plug is properly connected.
Stop loading and monitor the temperature with no load for a while.
Disconnect the module from AC power for 1 minute, and reboot the module after making sure there is no power in it; re-plug the fan if the problem still exists; replace the fan if the problem still exists after last step; check the fan drive circuit if the problem still exists after last step.
Make sure the module and the charging pile are properly earthed. Disconnect the module from AC power for 1 minute and reboot the module after making sure there is no power in the module.
Make sure the module load is in normal condition. Check whether the load is above normal level and the module limited current is below the normal level.
Make sure the module wiring and grid input voltage is in normal condition.
Make sure the module input wiring and grid voltage is in normal condition.
Check whether there is fuse blown in module DC board output end.
It stands for output under-voltage. Make sure the module load is in normal condition. Check whether the load is above normal level and the module limited current is below the normal level.
For module idle for more than 3 days, it should be stored with packaging material with desiccant in dry and ventilated environment. For module idle for more than 6 months, reversibly connect the module polarities for an hour. After that, no-load running in 500V for 4 hours.
The modules should be sent back to supplier for repairing if there is any abnormality after last step.